Ventilation in Schools - Elementary Schools A-M

YRDSB is optimizing air quality in schools through improved ventilation and filtration. This is a key element in the protective strategies being employed to reduce the risk of COVID-19 transmission and support healthier and safe learning environments. 

See below for information on ventilation in each elementary school (A-M), or use the links below to find your school:

Elementary Schools A-G

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes Yes
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 1

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes Yes
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 8

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

5Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 3

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 8

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 8

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 4

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 5

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Partial Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 17

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 1

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 1

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes Yes
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 4

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 10

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed No
Standalone HEPA filter units in place 8

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed No
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 5

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 8

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 8

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 5

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Partial Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 15

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 5

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 5

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 5

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed No
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Partial Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 31

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Partial Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 15

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 4

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 5

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 8

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 8

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes Yes
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 3

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 4

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 1

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 5

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Partial Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 28

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed Yes
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 5

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 3

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 8

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Elementary Schools H-J

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 8

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed No
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed No
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed No
Standalone HEPA filter units in place 3

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 9

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Non-Mechanical Ventilation (Natural Ventilation/Exhaust Only)
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 18

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Non-Mechanical Ventilation (Natural Ventilation/Exhaust Only)
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) No
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 27

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 5

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 8

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 3

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Partial Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed Yes
Standalone HEPA filter units in place 16

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 1

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Elementary Schools K-M

Ventilation System Partial Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 19

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed No
Standalone HEPA filter units in place 3

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 5

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

Ventilation System Mechanical Ventilation 
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed No
Standalone HEPA filter units in place 8

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed No
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 1

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 5

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 4

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 1

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 8

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Partial Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 27

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 1

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed No
Standalone HEPA filter units in place 6

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 1

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 4

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 9

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Partial Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 16

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Partial Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed N/A
Standalone HEPA filter units in place 4

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)

School Ventilation and Filtration Measures  
Ventilation System Mechanical Ventilation
Ventilation assessed Yes
Running ventilation systems longer Yes
Higher grade filters installed (MERV13) Yes
Increased frequency of filter changes No
Increased fresh air intake (windows and/or mechanical ventilation systems) Yes
Standalone HEPA** filter units deployed in portables, as needed No
Standalone HEPA filter units in place 7

 

*Some measures may not be feasible within the context of a school facility/site and related building systems.

**High-Efficiency Particulate Air (HEPA)